Application
TSM9 moulded case circuit breaker supplied with rated insulation voltage 1000V is used for circuit of AC 50/60Hz, rated operating voltage AC 690V and rated operating current up to 1600A for infrequent changing over and starting of the motors.
Equipped with the protection devices against over current, short circuit and under voltage, the product is capable of preventing damage of circuits and supply units. The product can be used to replace a load switch with isolation function. The products comply with IEC60947-2.
The product is equipped with an intelligent controller with LCD display. Rated operating current, overload setting current, short circuit delay current, short circuit instantaneous current, tripping time, as well as short circuit instantaneous three-stage protection and under voltage protection can be set in advance.
The product is also equipped with RS485 communication interface and MODBUS-RTU protocol, DL/T 645 protocol.
The following indication can be chosen by the users:
Remote signal: breaking closing, tripping, alarm and fault status indication;
Remote control: breaking, closing, resetting;
Telemetry: three phase current and N phase current, grounding current, trip memory
function, and functions such as querying trip recording parameters.
Specification
Model | TSM9-100 | TSM9-160 | TSM9-250 | TSM9-400 | TSM9-630 | TSM9- 1600 |
Number of Poles | 3P, 4P | |||||
Shell Frame Maximum Rated Current Inm(A) | 100 | 160 | 250 | 400 | 630 | 1600 |
Rated Current ln(A) | 12.5,16,20, 25,32,40, 50,63,80, 100 |
16,20,25, 32,40,50, 63,80,100, 125,160 |
100,160, 180,200, 225,250 |
250,315, 350,400 |
400,500, 630 |
630,800, 1000,1250, 1600 |
Rated Insulation Voltage Ui | 1000V | |||||
Rated Impulse Withstand Voltage Uimp | 8000V | |||||
Rated Voltage Ue | AC 400V/415V 50/60HZ | |||||
Flying arc Distance (mm) | 0 | |||||
Rated Ultimate Short Circuit Breaking Capacity Icu(kA) 400/415V | L=50kA, M=85kA, H=100kA | L=50kA | ||||
Rated Service Short Circuit Breaking Capacity lcs(kA) 400/415V | Ics=100%Icu | |||||
Utilization Category | A | A | A | B | B | B |
Rated Short Time Withstand Current lcw (kA)(1s) | / | 5.0kA/1s | ||||
Electrical Life (times) | 10000 | 8000 | 8000 | 6000 | 5000 | 1500 |
Mechanical Life (times) | 20000 | 20000 | 20000 | 10000 | 10000 | 10000 |
Micrologic 5.0E measurement function
Protection Function |
Current (A) | Overload protection | |
Short circuit short delay protection | |||
Instantaneous action protection | |||
(4P) Netural line protection | |||
Grounding protection | |||
Current unbalance protection | |||
Overload preliminary warning | |||
Voltage (V) | Breaking zero | ||
Voltage unbalance protection | |||
Over frequency and under frequency protection | |||
Phase sequence protection | |||
Measurement Function |
Current (A) | Phase current and neutral line current | |
Average phase current | |||
The maximum value of phase current and neutral line current | |||
Percentage of ground faults | |||
Interphase unbalanced current value | |||
Voltage (V) | Line voltage | ||
Phase voltage | |||
Average line voltage | |||
Average phase voltage | |||
Unbalanced line voltage, unbalanced phase voltage | |||
Phase sequence | |||
Frequency (Hz) | |||
Power | Active | ||
Reactive | |||
Apparent | |||
Power factor | |||
Electricity | Active (kWh), Reactive (kVARh), Visual (kVAh) | ||
Maintenance Function |
The figures record | Times of all kinds of prection of tripping | |
MAX/MIN value record | Max/Min record of current and voltage from each phase | ||
Record | Trip ,alarm and deflection record | ||
Contact wear | Contact abrasive wear record | ||
Times of operation | The times of operation record | ||
RTC Function | Realtime clock | ||
Auxiliary alarm detection function function | Auxiliary alarm detection, display the state of circuit breaker | ||
Electric operation control function | Remote electric operation control function | ||
Human and machine interaction | LED display | ||
LCD display | |||
Enter setting | |||
Communication function | Modbus RTU DL/T645 |
Tel: +86-577-88671000
E-mail: ceo@tosun.com
Skype: tosunelectric
Wechat: +86-139 6881 9286
WhatsApp: +86-139 0587 7291
Address: Room No.1001 Wenzhou Fortune Center,Station Road, Wenzhou, China
WhatsApp us