Applications Designed for monitoring level in wellss , basins , reservoirs , tanks ...... Feature In one device you can choose the following configurations: 2 level control mode 1 level control mode Choice of function PUMP UP , PUMP DOWM. Sensitivity adjustable by a potentiometer(5-100kΩ) Galvanically separated supply voltage AC/DC 24-240V Relay status is indicated by LED. 1-MODULE , DIN rail mounting. Technical Parameters
Model | TRL8-01 | TRL8-02 |
Function | 2 level control mode | 2 or 1 level control mode |
Supply terminals | A1-A2 | |
Voltage range | AC/DC 12-240V(50-60Hz) | |
Input | max.2VA | |
Supply voltage tolerance | -15%;+10% | |
Sensitivity(input resistance) | Adjustable in range 5 kΩ-100kΩ | |
Voltage in electrodes | max.AC 5V | |
Current in probe | AC<0.1mA | |
Time response | max.400ms | |
Max.capacity length | 800 m(sensitvity 25kΩ),200 m(sensitivity 100kΩ) | |
Max.capacity of probe cable | 400 nF(sensitvity 25kΩ),100 nF(sensitivit 100kΩ) | |
Time delay(t) | Adjustable,0.1-10s | |
Accuracy in setting(mechanical) | ±10% | |
Temperature coefficient | 0.05%/°C,at=20℃(0.05%°F,at=68°F) | |
Output | 1XSPDT | |
Current rating | 10A/AC1 | |
Switching voltage | 250VAC/24VDC | |
Min.breaking capacity DC | 500mW | |
Output indication | Red LED | |
Mechanical life | 1×10000000 | |
Electrical life(AC1) | 1×100000 | |
Reset time | max.200ms | |
Operating temperature | -20°℃ to+55°C(-4°F to 131°F) | |
Storage temperature | -35°C to +75℃(-22°℉ to 158°℉) | |
Standards | EN 60255-1 |
Dimension