Aplikasi
HGLD series dual power automatic changeover switch is suitable in electrical system with AC 50/60Hz, rated insulation voltage up to 1000V, rated voltage up to 440V, conventional heat current up to 3200A. The items are widely used in varieties of hospital, building, bank, airport, coal mine, telecom, freeway, military installations etc.
Spesifikasi
Rated heating current (A) | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 | |
Rated insulation voltage | 750V | 1000V | ||||||||||
Rated impulse withstand voltage | 8 kV | 12kV | ||||||||||
Rated working current (A) |
AC-31A | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 |
AC-35A | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 | |
AC-33A | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 | |
Rated short-term withstand current | 7 kA | 9 kA | 13kA | 50kA | 55kA | |||||||
Rated limited short circuit current | 100kA | 70kA | 100kA | 120kA | 80kA | |||||||
Control power supply voltage | DC24V , 48V , 110V , AC220V | |||||||||||
Conversion time (s) | 0.5 | 1 | 1.1 | 1.2 | 1.25 | 2.45 |
Telp: +86-577-88671000
Surel: ceo@tosun.com
Skype: tosunelektrik
Telepon: +86-139 6881 9286
WhatsApp: +86-139 0587 7291
Alamat: Kamar No.1001 Wenzhou Fortune Center, Station Road, Wenzhou, Tiongkok
WhatsApp kami