TSAF1 Arc Fault Detection Device

Informasi Dasar
  1. Model TSAF1-63; TSAF1-40

Deskripsi Produk

Aplikasi

AFDDs detect and automatically disconnect arc faults which occur in damaged or crushed cables,
loose terminations and ageing installations where the insulation performance degrades over time. 
It can provide over current protection, short circuit protection, residual current protection and arc 
fault protection as well. The products comply with IEC62606 and IEC61009-1.

Spesifikasi

Model TSAF1-40 TSAF1-63
Nilai Arus 6A, 10A, 16A, 20A,
25A, 32A, 40A
6A, 10A, 16A, 20A, 25A,
32A, 40A, 50A, 63A
Jenis Jaringan AC  ~  /A  ~
Tegangan Terukur 230/240V~
Maximum Operating Voltage 1.1Un
Minimum Operating Voltage 180V
Kode Kurva B, C
Rated Residual Making and Breaking Capacity (I△m) 3000A
Rated Residual Operating Current (I△n) Arus listrik 30mA, 100mA, 300mA
Rated Short Circuit Capacity (Icn) 6000A
AFDD Test Means Automatic test function as per IEC 62606
Classification as Per IEC 62606 4.1.2 – AFDD unit integrated in a protective device
Ambient Operating Temperature -25°C ~ 40°C
AFDD Ready Indication Single LED Indication
Over voltage Function Over voltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.
LED indication of over voltage trip will be provided on product re-latch.
Self Test Interval 1 Hour

 

Ukuran