Parameters and features
Standard: IEC60269-1 & IEC60269-6
Rated voltage: DC1000V
Rated current: 20A
Breaking capacity: 33 KA
Operating class: gPV
Protection objects: It is used in the photovoltaic combiner box to provide safe and reliable protection for overload and short-circuit current faults of PV modules and PV arrays.
Applicable environment: Temperature, -5°C~+40°C;
Humidity, less than 90%.
Specification
Fuse link | Fuse base | |||||
Model | Rated current(A) | l²t(A²s) | Power loss (W) 1.0 In | Model | Rated current(A) | |
Melting Clearing | ||||||
TSPV-25 | 1 | 5 | 16 | 0.9 | TSPV-25B TSPV-25BX | 32A |
2 | 8 | 32 | 1.0 | |||
3 | 10 | 48 | 1.3 | |||
4 | 13 | 65 | 1.5 | |||
5 | 22 | 86 | 1.6 | |||
6 | 32 | 1 00 | 1.8 | |||
8 | 42 | 1 35 | 2.1 | |||
10 | 50 | 1 52 | 2.3 | |||
12 | 57 | 1 88 | 2.7 | |||
15 | 60 | 230 | 3.0 | |||
20 | 80 | 310 | 3.6 | |||
25 | 120 | 420 | 4.5 | |||
32 | 185 | 660 | 5.0 |
Average Characteristics Curve
Dimensions
Parameters and features
Standard: IEC60269-1 & IEC60269-6
Rated voltage: DC1500V
Rated current: 32A
Breaking capacity: 25 KA
Operating class: gPV
Protection objects: It is used in the photovoltaic combiner box to provide safe and reliable protection for overload and short-circuit current faults of PV modules and PV arrays.
Applicable environment: Temperature, -5°C~+40°C;
Specification
Fuse link | Fuse base | |||||
Model | Rated current (A) | l²t(A²s) | Power loss (W) 1.0 ln |
Model | Rated current (A) | |
Melting | Clearing | |||||
TSPV-32 | 2 | 3.5 | 12 | 2.2 | TSPV-32B TSPV-32BX | 32A |
3 | 8 | 18 | 2.5 | |||
4 | 16 | 35 | 2.8 | |||
5 | 30 | 66 | 3.0 | |||
6 | 46 | 130 | 3.3 | |||
8 | 55 | 200 | 3.8 | |||
10 | 70 | 270 | 4.5 | |||
12 | 95 | 360 | 5.0 | |||
15 | 130 | 400 | 5.7 | |||
20 | 220 | 750 | 6.8 | |||
25 | 350 | 1 000 | 7.2 | |||
32 | 480 | 1 600 | 8.2 |
Average Characteristics Curve
Dimensions