Applications ● Control for connection of moving equipment (like site equipment, agricultural equipment, refrigerated trucks). ● Control for protection of people and equipment against reverse running. ● Normal/emergency power supply switching. ● Protection against phase failure of driving load. ● Control its own supply voltage (true RMS measurement). ● Set 8 kinds rated operating voltage through knob Function
Model | Over-voltage | Under-voltage | Asymmetry | Delay time | Phase sequence | Phase failure |
TRV8-03 | – | – | – | – | ● | ● |
TRV8-04 | 2%…20% | -20%…2% | – | 0.1s…10s | ● | ● |
TRV8-05 | 2%…20% | -20%…2% | -8% | 0.1s…10s | ● | ● |
TRV8-06 | 2%…20% | -20%…2% | 5%…15% | 2s | ● | ● |
TRV8-07 | – | – | 5%…15% | 2s | ● | ● |
TRV8-08 | 15% | -15% | 8% | 2s | ● | ● |
Specification
Voltage Model | M460 | M265 | |
Function | Monitoring 3-phase voltage | ||
Monitoring Terminals | L1-L2-L3 | L1-L2-L3-N | |
Supply Terminals | L1-L2 | L1-N | |
Voltage Range (V) | 220-230-240-380-400 -415-440-460(P-P) | 127-132-138-220-230 -240-254-265(P-N) |
|
Rated Supply Frequency | 45Hz-65Hz | ||
Measuring Range | 176V-552V | 101V-318V | |
Supply Indication | Green LED | ||
Output Indication | Red LED | ||
Switching Voltage | 250VAC/24VDC | ||
Current Rating | 10A/AC1 | ||
Reset Time | 1000ms |
Dimension
WhatsApp us